Medium
Capacity Rack Power System –48V, 100A to 3000A
|
|
|
SALIENT
FEATURES
- Modular
Rack Power systems up to 3000A Capacity with
flexible configuration using 100A rectifier
Modules.
- AC
Mains Connection (Three Phase).
- Near
Unity Power Factor.
- Near
sinusoidal Input Current.
- Provides
better than 90% Efficiency at full load, Nominal
input Voltage.
- Low
Input Distortion.
- Efficient
Monitoring and Control Module to monitor system
parameters provide extensive information on
System Status and Alarm Conditions.
- Alphanumeric
display Showing Load and Battery Voltage and
Current and other system parameters.
- Detection
and Indication of Alarm Conditions.
- Customer
specific Battery Isolation System for 2,3 or
4 batteries.
- Temperature
Compensation of battery Float Voltage.
- Configurable
DC Distribution.
- Automatic
switch over from Auto Charge Mode to Float Mode
or Vice Versa
- Battery
Interconnection Module equipped with LVD (optional)
Contractor for Battery and Load Current Monitoring
Shunts.
- Optional
two stage Low Voltage Disconnect.
- High
AC Voltage Disconnect.
- Forwarding
of Alarm Conditions to remote location.
- Standard
19” rack size.
- Type
Approved to TEC / BSNL Specifications.
|
|
SYSTEM
CONFIGURATIONS
The Rack Power System consists of: -
19”
Master Rack with Monitoring & Control Module
(MCM).
19”
Slave Rack with AC Distribution Module.
100
Amps Switch Mode Rectifier as Basic Power Module.
Battery
Isolated System (Customized)
Interconnection
Cable & Bus bar Set
DCDB
Rack (as per customer requirement)
|
TECHNICAL
SPECIFICATIONS
|
| AC
Input |
Nominal 400V AC, Three Phase. AC Range-340
– 440V, Frequency - 48 – 52Hz. |
| DC
Output |
Float
Mode-48 – 56V DC, Charge Mode- 51 – 56V DC |
| Power
factor |
Near Unity. |
| Offered
Capacity |
Up
to 3000A for 100A SMRs. |
| DC
Distribution |
Custom
configurable as per requirement. |
| LVD |
Single
/ Two Stage |
| Disconnect
Voltage |
44.4V(Reconnect 51.5V) |
| Temperature
Compensation |
3mV
/ degree Centigrade / cell. |
| Metering |
·
AC
Input Voltage.
·
Load
Voltage
·
Battery
Voltage
·
Load
Current
·
Battery
Current
·
System
Current.
|
| Alarms
and Visual Indications : |
·
AC
Available
·
AC
Abnormal
·
Load
UV
·
Load
OV
·
Over
Load
·
Rectifier
Fail
·
Float
/ Charge
·
MBD
·
LVD
·
Battery
isolation
|
| Status |
LED Indications for : -
·
AC
Available.
·
System
OK
·
LVD.
·
System
on Float Mode
·
System
on Charge Mode.
|
| Remote
Alarms |
Normally
both open & close potential free contacts are
provided on 25-pin D-connector
for the following Alarms: -
·
Load
Over Voltage.
·
Load under Voltage.
·
AC
Abnormal.
·
Low
Voltage Disconnect.
·
System
Faulty.
·
Rectifier
Fail.
·
CB-Trip
Battery isolated
·
Mains
– ON / Battery Discharge.
|
| Remote
ON / OFF |
Rectifier
can be disabled externally. |
| Remote
Charging |
SMRs
can be made to operate in Auto Change Mode externally.
|
| Cooling |
Rectifiers
are forced air-cooled. |
| Environment
Specifications |
Temperature : 0 – 50 degree centigrade, Humidity
: 95% Max. |
| Physical
Dimensions (Maximum) : |
Rectifier
Height : 200 mm.
Width : 485 mm.
Depth : 450 mm.
Weight : 24 Kg. (approx).
|
| Rack |
Multi Rack Configuration with each rack of dimension
as under :
Height : 2167 mm (45 RU) / 1633 mm (33
RU).
Width : 600 mm.
Depth : 600 mm.
|
|
|
|
|